Category 7 F/FTP 100 Ohm Horizontal LAN Cables DataLink 600

TRANSMISSION PROPERTIES AND ELECTRICAL SPECIFICATIONS
FREQ. Insertion Loss NEXT PS NEXT EL FEXT PS EL FEXT RL TCL EL-TCL PS ANEXT PS AFEXT
 MHz dB/100m dB dB dB/100m dB/100m dB dB dB dB dB
  Max Min Min Min Min Min Min Min Min Min
1 NS 78.0 75.0 78.0 75.0 20.0 40.0 35.0 67.0 67.0
4 3.74 78.0 75.0 83.3 80.3 23.0 40.0 23.0 67.0 67.0
8 5.24 78.0 75.0 77.2 74.2 24.5 40.0 16.9 67.0 67.0
10 5.86 78.0 75.0 75.3 72.3 25.0 40.0 15.0 67.0 67.0
16 7.41 78.0 75.0 71.2 68.2 26.0 38.0 10.9 67.0 67.0
20 8.29 78.0 75.0 69.3 66.3 25.0 37.0 9.0 67.0 67.0
25 9.29 78.0 75.0 67.3 64.3 24.3 36.0 7.0 67.0 65.2
31.25 10.41 78.0 75.0 65.4 62.4 23.6 35.1 5.1 67.0 63.3
62.5 14.88 75.5 72.5 59.4 56.4 21.5 32.0 NS 67.0 57.3
100 19.02 72.4 69.4 55.3 52.3 20.1 30.0 NS 67.0 53.2
150 23.56 69.8 66.8 51.8 48.8 18.9 28.2 NS 67.0 49.7
200 27.47 67.9 64.9 49.3 46.3 18.0 27.0 NS 67.0 47.2
250 30.97 66.4 63.4 47.3 44.3 17.3 26.0 NS 67.0 45.2
300 34.19 65.2 62.2 45.8 42.8 17.3 NS NS 67.0 43.7
400 40.01 63.4 60.4 43.3 40.3 17.3 NS NS 67.0 41.2
500 45.26 61.9 58.9 41.3 38.3 17.3 NS NS 67.0 39.2
600 50.10 60.7 57.7 39.7 36.7 17.3 NS NS 65.8 37.6


Characteristic Impedance 100±5 Ohm @ 1-600 MHz
Resistance Unbalance 2% max.
Capacitance 45 pF/m nom. @ 1 KHz
Cap. Unbalance (Wire to Ground) 1500 pF/Km max. @ 1 KHz.
Voltage Rating 72 Vdc max.
Dielectric Strength 700 Volts/1 minute min rms
Velocity of Propagation (NVP) 77-80%
Propagation Delay 500+36/f1/2
Delay Skew 25 nS/100m max @ 1-600 MHz.
Insulation Resistance 5000 MegaOhm•Km min. @ 500 Vdc
Coupling Attenuation IEC 61156-5 Type 1b
Screening Attenuation 60 dB min @ 30-600 MHz
Transfer Impedance IEC 61156-5 Grade 1


ORDERING INFORMATION
HCS P/N Description OD
mm
Weight
Kg/Km
Cal. Value
Kj/m
Packaging Notes
H07-F0452-DP 4x2x23# F/FTP CAT 7 LS0H Gray 7.2 53 660 500m Drum -
H07-F0452-DM 4x2x23# F/FTP CAT 7 LS0H Gray 7.2 53 660 1000m Drum -
H07-F0854-DP 2x(4x2x23#) CAT 7 F/FTP LS0H Gray 7.2x14.4 106 1320 500m Drum FIG-8
H07-F0854-DM 2x(4x2x23#) CAT 7 F/FTP LS0H Gray 7.2x14.4 106 1320 1000m Drum FIG-8
Flame Test conformance:                  F=0: IEC 60332-1     F=C: IEC 60332-3-24     F=D: IEC 60332-3-25